List of Action Numbers
3-849
©
Siemens AG, 2006. All rights reserved
SINUMERIK, SIMODRIVE Diagnostics Manual (DA), Edition 11/2006
No. 98
No. 99
No. 100
No. 101
No. 102
No. 103
Explanation
Extended stop and retract
Cause
-
Remedy
-
Explanation
Block search (general) is currently being activated (negative acknowledgement may be
output for PI service).
Cause
-
Remedy
-
Explanation
Integrated block search, i.e., a block search is restarted on a stopped program.
Cause
-
Remedy
-
Explanation
External zero offset is activated via the PLC. Movement is stopped, a Reorg is per-
formed, the interpreter is switched over and then selected using REPOS and continued
automatically.
Cause
1. The channel is not in AUTO or MDA
2. The channel is stopped and the current block cannot be reorganized.
Remedy
−
Select Auto or MDI
−
Activate a block change until the NC block can be reorganized.
Explanation
Single block type 3 is activated. With single block type 3, a stop is performed at all main
blocks. Unlike single block type 1, the part program command SBLOF is ignored.
Cause
-
Remedy
-
Explanation
Stopping of a single axis movement (VDI signal)
Cause
The axis is not controlled by the PLC. (exception old reaction with oscillation axis).
Remedy
-