11/2006
List of Action Numbers
3-853
©
Siemens AG, 2006. All rights reserved
SINUMERIK, SIMODRIVE Diagnostics Manual (DA), Edition 11/2006
No. 126
No. 127
No. 128
No. 129
No. 130
Explanation
Implicit change of operating mode to Automatic at the end of a Jog motion in Automatic
mode
See also: $MN_JOG_MODE_MASK
Cause
1. A channel has exited the mode group due to an interrupt.
2. Overstore
Remedy
−
Abort the program with the Reset key or wait until the interrupt is terminated
−
Deselect overstore
Explanation
Simulation block search should be initiated, i.e., the calculation results are only dis-
played on the HMI and there is NO traversing even after the block search.
Cause
1. The channel is not in RESET
Remedy
−
Press Reset key
Explanation
Refusal to execute program area
Cause
1. The channel is not in RESET
2. The channel is not in Automatic mode
Remedy
−
Press Reset key
−
Switch to Automatic mode
Explanation
Refusal to select PI service syntax check "_N_CHKSEL"
Cause
The channel is not in RESET
Remedy
Press Reset key
Explanation
Refusal to start PI service syntax check "_N_CHKRUN"
Cause
The channel is not in RESET
Remedy
Press Reset key