4065
Buffered memory was restored from backup medium (potential loss of
data!)
Definitions:
Only occurs with PC-NC. A possible data integrity error was detected in the buffered memory during
power-up. The buffered memory was initialized with the last backup copy. Changes in the buffered
memory, which have been made since the last backup copy update, have been lost. Backup copies
of the buffered memory are updated (on the hard disk) every time the control is shut down normally.
!! Only for 802D: The reason for this procedure is that the backup time is exceeded. Make sure that
the required operating time of the control corresponds to the specifications in your Installation & Start-
up Guide. The current backup copy of the buffered memory has been created by the last internal data
backup via the "Save data" softkey on the HMI.
Reaction:
NC not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy:
Start the control again.
Program
Continuation:
Switch control OFF - ON.
4066
Buffered memory of FFS restored from backup medium (potential loss of
data!)
Definitions:
For PC-NC: A possible data integrity error was detected in the FFS memory during power-up. The FFS
memory was initialized with the last backup copy. Changes in the FFS memory, which have been
made since the last backup copy update, have been lost.
!! Only for PC-NC: Backup copies of the buffered memory are updated (on the hard disk) every time
the control is shut down normally.
Reaction:
NC not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy:
Start the control again.
Program
Continuation:
Switch control OFF - ON.
4070
Normalizing machine data has been changed
Definitions:
The control uses internal physical units (mm, degrees, s, for paths, velocities, acceleration, etc.).
During programming or data storage, some of these values are input and output using different units
(rev./min, m/s2, etc.).
The conversion is carried out with the scaling factors that can be entered (system-spefic MD array
10230 SCALING_FACTORS USER_DEF[n] (n ... index number 0 - 10), when the corresponding
masking bit is set to "1".
If the masking bit is set to "0" then scaling takes place with the internal standard factors.
The following machine data influence the scaling of other MDs:
- 10220: SCALING_USER_DEF_MASK
- 10230: SCALING_FACTORS_USER_DEF
- 10240: SCALING_SYSTEM_IS_METRIC
- 10250: SCALING_VALUE_INCH
- 30300: IS_ROT_AX
If these data are modified, the NCK must be powered up again. Only then will the input of dependent
data be performed correctly.
Reaction:
Alarm display.
Remedy:
Please inform the authorized personnel/service department. If the alarm has been displayed after
downloading an MD file which is consistent within itself, then the download operation must be
repeated with a new NCK power-up. (The file contains scaling-dependent machine data in front of the
scaling factors).
Program
Continuation:
Clear alarm with the Delete key or NC START.