Overview of Alarms
11/2006
NCK alarms
2-178
©
Siemens AG, 2006. All rights reserved
SINUMERIK, SIMODRIVE Diagnostics Manual (DA), 11/2006 Edition
12553
Channel %1 block %2 name %3 option/function is not active
Parameters:
%1 = Channel number
%2 = Block number, label
%3 = Source symbol
Definitions:
The option (if $MN_NC_LANGUAGE_CONFIGURATION = 1) or the NC function (if
$MN_NC_LANGUAGE_CONFIGURATION = 3)
related to this language command is not active.
But the name of the language command is known.
Each programming of this language command is rejected with this alarm.
Reaction:
Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy:
Press the NC Stop key and select the "Compensation block" function by pressing the PROGRAM
CORRECT softkey. The cursor positions itself on the incorrect block.
- Correct the name used (in the case of a typing error).
- Activate the NC function (if a language command of an inactive function has been programmed).
- Enable the option required (if a language command of a function with a non-enabled option has been
programmed).
See also $MN_NC_LANGUAGE_CONFIGURATION.
Program
Continuation:
Clear alarm with NC START or RESET key and continue the program.
12554
Channel %1 block %2 replacement cycle %3 for the predefined
procedure is missing.
Parameters:
%1 = Channel number
%2 = Block number, label
%3 = Cycle name
Definitions:
The replacement cycle that is to be called instead of the predefined procedure
is not present / unknown in the control.
Reaction:
Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy:
Press the NC stop key and select the "Compensation block" function by pressing the PROGRAM
CORRECT softkey. The cursor will position itself in the faulty block.
- Correct the name used for the predefined procedure (write error)
- Or load the replacement cycle into one of the cycle directories (+ restart)
- Or set the machine data bit for the predefined procedure in $MN_COUPLE_CYCLE_MASK to 0 so
that the predefined procedure is executed again.
Program
Continuation:
Clear alarm with NC START or RESET key and continue the program.