NCK alarms
11/2006
Overview of Alarms
2-113
©
Siemens AG, 2006. All rights reserved
SINUMERIK, SIMODRIVE Diagnostics Manual (DA), 11/2006 Edition
10658
Channel %1 axis %2 impermissible axis status.
Parameters:
%1 = Channel number
%2 = Error ID and gantry unit.
Definitions:
%2 error ID and gantry unit
- %2 = 30XX => gantry group cannot be closed, as not all gantry axes
are available in one channel.
- %2 = 40XX => gantry group cannot be closed, as the gantry axes
have different axis states; the axis is assigned to the PLC, for example.
- %2 = 50XX => gantry group is to change the channel due to a PLC request;
not all gantry axes are known in the new channel.
- %2 = 60XX => gantry group is to be transferred to channel due to an NC program request,
but the channel does not know all the gantry axes.
Reaction:
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy:
Error ID:
- %2 = 30XX => assign all gantry axes to the current channel, for example via axis change.
- %2 = 40XX => set all axes of the gantry group to the same axis state,
for example assign all axes to the NC program, or assign all axes to the PLC.
- %2 = 50XX => make all gantry axes known to the required channel.
- %2 = 60XX => make all gantry axes known to the required channel.
:end
Program
Continuation:
Clear alarm with the RESET key. Restart part program
10700
Channel %1 block %2 NCK protection zone %3 violated during automatic
or MDI mode
Parameters:
%1 = Channel number
%2 = Block number
%3 = Protection zone number
Definitions:
The workpiece-related NCK protection zone has been violated. Note that another tool-related
protection zone is still active. The workpiece-related protected area can be traversed after a new NC
Start.
Reaction:
Local alarm reaction.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy:
Protection zone can be traversed after a new NC Start.
Program
Continuation:
Clear alarm with NC START or RESET key and continue the program.
10701
Channel %1 block %2 channel-specific protection zone %3 violated
during automatic or MDI mode
Parameters:
%1 = Channel number
%2 = Block number
%3 = Protection zone number
Definitions:
The workpiece-related channel-specific protection zone has been violated. Note that another tool-
related protection zone is still active. The workpiece-related protected area can be traversed after a
new NC Start.
Reaction:
Local alarm reaction.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy:
Protection zone can be traversed after a new NC Start.
Program
Continuation:
Clear alarm with NC START or RESET key and continue the program.