Configuration Options in Zones
General rules
Regardless of the configuration of the ET 200iSP in hazardous areas or in the safe area, the
following rules apply:
The ET 200iSP distributed IO station can only be operated on the intrinsically safe PROFIBUS
RS 485-IS:
1. An RS 485-IS coupler (field bus isolating transformer) is always required
2. Identification of PROFIBUS DP as Ex i (not only for potentially explosive areas)
3. Marking of the cables/wires to the actuators and sensors as EEx i (for example, using the
color light blue).
WARNING
Connect only intrinsically safe devices to PROFIBUS RS 485-IS
All devices connected to PROFIBUS RS 485-IS must be intrinsically safe.
Do not connect voltage measuring devices, oscillographs, and bus testers to
PROFIBUS RS 485-IS.
Rules for configuring the ET 200iSP in Zone 1:
If you use the ET 200iSP in zone 1, you must adhere to the following rules:
1. Installation of ET 200iSP in an enclosure with type of protection Ex e (increased safety).
(see section "Rules for installation (Page 83)", see appendix "Order numbers (Page 335)").
2. Isolation of PROFIBUS DP by means of RS 485-IS coupler (see Appendix "Order
Numbers (Page 335)"). The RS 485-IS Coupler ensures protection class Ex i of PROFIBUS
DP in potentially explosive areas. You can install the RS 485-IS Coupler in zone 2 potentially
explosive areas or in safe areas.