Technical specifications
Diagnostics function
Yes
● Group error
● Bus monitoring
● Redundancy
Red "SF" LED
Red "BF" LED
Yellow "ACT" LED
● Monitoring of the power supply voltage of the
electronic circuit
Green "ON" LED
● Monitoring of the power supply at the Power
Supply PS 1
● Monitoring of the power supply at the Power
Supply PS 2
Green "PS1" LED
green "PS2" LED
Safety data
See EC-type-examination certificate
KEMA 04ATEX1243
Maximum values for PROFIBUS RS 485-IS interface:
● Uo
±3.9 V
● Io
±136 mA
● Po
132 mW
● U
i
±4.2 V
11.2
Parameters for the IM 152
Parameter
The procedure for setting parameters is described in the Chapter "Commissioning".
Table 11-1
Parameters for the interface module IM 152
IM 152 parameters
Range of values
Default
Applicability
Operation at Preset <> Actual
Configuration
● disable
● enable
disable
ET 200iSP
Self-diagnosis
● disable
● enable
disable
ET 200iSP
Redundant Power Supply di‐
agnostics
● No redundant power
supply
● Redundant Power Supply
● Redundant Power Supply
required
No redundant power supply
ET 200iSP
Diagnostic interrupts
1)
● disable
● enable
disable
ET 200iSP
Hardware interrupts
1)
● disable
● enable
disable
ET 200iSP
Interface module
11.2 Parameters for the IM 152
ET 200iSP
230