Step 4
Select Insert > Station and then click SIMATIC 400 Station in the list. An icon with the name
SIMATIC 400(1) appears in the right-hand pane of the project window.
Step 5
Now double-click on the icon of the SIMATIC 400 station in the SIMATIC Manager. An icon
labeled "Hardware" now appears in the right-hand pane of the window. Double-click on this
icon. HW Config opens.
Step 6
If no catalog with components is displayed on the right-hand side of the window, activate the
display by selecting View > Catalog in the menu.
Expand the SIMATIC 400 folder and RACK‑400 folder until you see UR1. Double-click on this
icon.
Step 7
Select slot 1 (it changes to blue) and then return to the catalog and open the folders SIMATIC
400, PS 400 and Standard PS 400 until you can see PS 407 4A. Double-click on this icon. The
power supply module now occupies slot 1.
Step 8
Next, select slot 3, then go to SIMATIC 400 via CPU 400, CPU 416-3 DP, and
6ES7416‑3XR05‑0AB0. A double-click opens a window titled "Properties-PROFIBUS interface
DP". Acknowledge this with OK. The CPU is entered in slot 2.
Step 9
In the lower left-hand window, locate the row labeled DP and select it. Right-click on the row
and select Object Properties. The "Properties DP" dialog opens. Click the Properties button
and in the next dialog, click New. A new DP subnet operating at 1.5 Mbps is created. Now
confirm by clicking OK three times in succession.
Commissioning guideline
2.9 Configuring the Example
ET 200iSP
36
Operating Instructions, 11/2017, A5E00247483-07