Procedure for Configuration and Parameter Assignment
1. Start SIMATIC Manager.
2. Configure the ET 200iSP with HW Config.
– Create a new project
– Drag modules from the hardware catalog to the configuration table
3. Configure the time stamping (option).
4. Double-click on the first module of the ET 200iSP in the configuration table and set the
parameters.
5. Set the parameters for the remaining ET 200iSP modules.
6. Save the configuration, or download it to the DP master.
6.3
Project Engineering with GSD File and SIMATIC PDM
Properties
ET 200iSP is integrated as a DPV0 or DPV1 slave.
Prerequisites
● The required software has been installed on the PG/ PC or PCS 7-ES.
● You need GSD file SI028110.GSE. These can be downloaded from the Internet at Service
& Support (
http://www.siemens.com/automation/service&support
)
The GSD file is integrated into the configuration software as described below:
Note
The GSD file for the ET 200iSP is based on Revision 4. Result: Not all parameters are
available in COM PROFIBUS.
Make sure that your configuration tool supports GSD files with Revision 4 so that all
parameters will be available.
STEP 7 version 4.02 or higher
COM PROFIBUS Version 5.0 or higher
1. Start STEP 7, open HW Config, then select
Options > Install new GSD file.
2. From the next dialog box, select the GSD file
you want to install and confirm with OK.
Result: The ET 200iSP appears in the
PROFIBUS-DP directory of the hardware
catalog.
1. Copy the GSD file from the ET 200iS to the
COM PROFIBUS directory: ...COMPB5\GSD
(default). Copy the bit map file to
the ...COMPB5\BITMAPS directory.
2. Start COM PROFIBUS, then select File > Read
in GSD file.
Result: The ET 200iSP is displayed in the
hardware catalog during the slave
configuration.
Commissioning and Diagnostics
6.3 Project Engineering with GSD File and SIMATIC PDM
ET 200iSP
Operating Instructions, 11/2017, A5E00247483-07