Components of the application example
The following table explains the components of the application example.
Table A-12
Components for overvoltage protection of the application example
Consecutive num‐
ber from the figure
Component
Meaning
①
Surge arrester 24 V supply
DEHNguard DG S 75 FM
Part No. 952 091* **
DEHNgap DGP C S FM
Part No. 952 035* **
Busbar MVS 1 2
Part No. 900 617* **
Pin-shaped terminal STAK 2x16
Part No. 900 589* **
Protection against indirect lighting effects and
overvoltages at zone transition 0
B
to 1 and 1
to 2
②
Surge arrester PROFIBUS RS 485-IS Blitzductor base
part BCT BAS EX,
Part. No. 920 301**
Blitzductor module BXT ML2 BD HF EX 6,
Part. No. 920 538**
Protection against indirect lighting effects and
overvoltages at zone transition 0
B
to 1 and 1
to 2
③
Surge arrester I/Os, depending on the number of dou‐
ble cores used
Blitzductor base part BXT BAS EX,
Part. No. 920 301**
Blitzductor module BXT ML4 BD EX 24,
Part. No. 920 381**
Protection against indirect lighting effects and
overvoltages at zone transition 0
B
to 1 and 1
to 2
④
Additional terminal for the shield connection of the bus
line
Discharging of interference currents
⑤
Equipotential bonding line 16 mm
2
Cu
Standardization of reference potentials
⑥
Equipotential bonding line 6 mm
2
Cu
Discharging of interference currents
* These components are designed for non-hazardous zones. If these units are installed in hazardous area Zone 1, the
components must be installed in a certified EX d enclosure (flameproof encapsulated). For additional information and ordering
refer to :