I&M
Access
Default
Explanation
DEVICE_INSTALL_ DATE
read / write (16
bytes)
---
Enter the installation date of the module
here.
M data 3: Index 4 (data record 234)
DESCRIPTOR
read / write (54
bytes)
---
Enter a comment on the module here.
1
The display of this I&M depends on the engineering software.
See also
Project Engineering with GSD File and SIMATIC PDM (Page 137)
3.11
Redundancy of the Power Supply
Properties
With the ET 200iSP, you can configure a redundant power supply PS. When one power supply
PS fails, the system fails over to the second power supply PS without interruption.
Requirements
● Terminal module TM-PS-A/ TM-PS-A UC
● Terminal module TM-PS-B/ TM-PS-B UC
● 2 x Power Supply PS
● IM 152 (V2.0 and higher)
Combination options of the power supply PS with TM-PS-A and TM‑PS‑B
TM-PS-A
TM-PS-B
PS 24 VDC*
PS 24 VDC*
* All product versions
Combination options of the power supply PS with TM-PS-A UC and TM‑PS‑B UC
TM-PS-A UC
TM-PS-B UC
PS 24 VDC*
PS 24 VDC*
PS 120/230 VAC**
PS 120/230 VAC**
PS 24 VDC*
PS 120/230 VAC**
* Product version 7 and higher
** Maximum output current, refer to technical specifications in the section
Power Supply PS 120/230 VAC
Configuration options
3.11 Redundancy of the Power Supply
ET 200iSP
60