13.11.2
Parameters relevant for 4 AI RTD, 4 AI TC analog electronics modules
4 AI RTD, 4 AI TC parameters
Table 13-36 4 AI RTD, 4 AI TC parameters
Parameter
Range of values
Default
Applicability
4 AI RTD
4 AI TC
Hardware interrupt (when limit value excee‐
ded)
1
● enabled
● disabled
disabled
Channel
Measuring method
---
● deactivated
● RTD 4-wire connection
● RTD 3-wire connection
● RTD 2-wire connection
● R 4-wire connection
● R 3-wire connection
● R 2-wire connection
RTD 4-wire con‐
nection
Channel
Measuring range
---
● Pt 100 standard range
● Pt 100 climate range
● Ni 100 Standard range
● Ni 100 climate range
● 600 Ω absolute
● 1000 Ω absolute
Pt 100 standard
range
Channel
---
Measuring range
● deactivated
● ±80 mV
● Type B [PtRh - PtRh]
● Type N [NiCrSi-NiSi]
● Type E [NiCr-CuNi]
● Type R [PtRh-Pt]
● Type S [PtPh-Pt]
● Type J [Fe-CuNi]
● Type L [Fe-CuNi]
● Type T [Cu - CuNi]
● Type K [NiCr-Ni]
● Type U [Cu-CuNi]
Type K [NiCr-Ni]
Channel
Group diagnostics
● enabled
● disabled
enabled
Module
Diagnostics overflow/underflow
● enabled
● disabled
enabled
Module
Diagnostics: wire break
● enabled
● disabled
enabled
Channel
Analog electronic modules
13.11 Parameters of the analog electronic modules
ET 200iSP
320
Operating Instructions, 11/2017, A5E00247483-07