Measuring range
600 Ω
Measuring range
1000 Ω
Units
Range
decimal
hexadecimal
(negative values are physically impos‐
sible)
-1
FFFF
H
Underrange
1
:
:
-4864
ED00
H
-32768
8000
H
Underflow
1
1
If connection is faulty
Measuring ranges for resistance thermometer Pt 100 standard
Table 13-15 SIMATIC S7 format: Measuring ranges Pt 100 standard in °C and °F
Pt 100
standard in
°C (1 digit =
0.1°C)
Units
Pt 100
standard in
°F (1 digit =
0.1 °F)
Units
Range
decimal
hexa‐
decimal
decimal
hexa‐
decimal
> 1000.0
32767
7FFF
H
> 1832.0
32767
7FFF
H
Overflow
1000.0
:
850.1
10000
:
8501
2710
H
:
2135
H
1832.0
:
1562.1
18320
:
15621
4790
H
:
3D05
H
Overrange
850.0
:
-200.0
8500
:
-2000
2134
H
:
F830
H
1562.0
:
-328.0
15620
:
-3280
3D04
H
:
F330
H
Nominal range
-200.1
:
-243.0
-2001
:
-2430
F82F
H
:
F682
H
-328.1
:
-405.4
-3281
:
-4054
F32F
H
:
F02A
H
Underrange
< - 243.0
-32768
8000
H
< - 405.4
-32768
8000
H
Underflow
Measuring ranges for resistance thermometer Pt 100 climate
Table 13-16 SIMATIC S7 format: Measuring ranges Pt 100 climate in °C and °F
Pt 100 cli‐
mate in °C
(1 digit =
0.01°C)
Units
Pt 100 cli‐
mate in °F
(1 digit =
0.01 °F)
Units
Range
decimal
hexa‐
decimal
decimal
hexa‐
decimal
> 155.00
32767
7FFF
H
> 311.00
32767
7FFF
H
Overflow
155.00
:
130.01
15500
:
13001
3C8C
H
:
32C9
H
311.00
:
266.01
31100
:
26601
797C
H
:
67E9
H
Overrange
130.00
:
-120.00
13000
:
-12000
32C8
H
:
D120
H
266.00
:
-184.00
26600
:
-18400
67E8
H
:
B820
H
Nominal range
Analog electronic modules
13.8 Representation of analog values
ET 200iSP
Operating Instructions, 11/2017, A5E00247483-07
295