Parameters
Range of values
Default
Applicability
Chatter monitoring: Number
of signal changeovers
2
2 to 31
5
Channel
1
Can only be assigned in HW Config and if the ET 200iSP is being operated as an S7 DP slave.
2
Parameter cannot be set unless chatter error diagnostics is enabled.
Parameters for 8 DI NAMUR, "2 Count/ 6 DI NAMUR" or "2 Count/ 6 Control" configuration
The following parameters can be set for the counter in addition to the "8 DI NAMUR"
configuration:
Table 12-18 Parameters for "2 Count/ 6 DI NAMUR" and "2 Count/ 6 Control"
Parameters
Range of values
Default
Applicability
Sensor type counter inputs ● Channel disabled
● NAMUR sensor
● Single contact, no load
resistance
NAMUR sensor
Channel
Mode for counter 1
● Standard counting function
● Periodic counting function
● Cascaded counting function
Standard counting function Channel 0
Mode for counter 2
● Standard counting function
● Periodic counting function
Standard counting function Channel 1
Parameters for 8 DI NAMUR, "2 Count/ 6 Control" configuration
The following parameters can be set for the counter in addition to the "8 DI NAMUR"
configuration:
Table 12-19 Parameters for "2 Count/ 6 Control"
Parameters
Range of values
Default
Applicability
Control channel
● Channel disabled
● NAMUR sensor
● Single contact, no load
resistance
NAMUR sensor
Channel
Digital electronic modules
12.5 Parameters of the digital electronic modules
ET 200iSP
Operating Instructions, 11/2017, A5E00247483-07