Ni 100 cli‐
mate in °C
(1 digit =
0.01°C)
Units
Ni 100 cli‐
mate in °F
(1 digit =
0.01 °F)
Units
Range
decimal
hexa‐
decimal
decimal
hexa‐
decimal
-60.01
:
-105.00
-6001
:
-10500
E88F
H
:
D6FC
H
-76.01
:
-157.00
-7601
:
-15700
E24F
H
:
C2AC
H
Underrange
< - 105.00
-32768
8000
H
< - 157.00
-32768
8000
H
Underflow
Measuring range for thermocouple: Type B
Table 13-19 SIMATIC S7 format: Measuring range type B in °C and °F
Type B in °C
Units
Type B in °F
Units
Range
decimal
hexa‐
decimal
decimal
hexa‐
decimal
> 2070.0
32767
7FFF
H
> 3276.6
32767
7FFF
H
Overflow
2070.0
:
1820.1
20700
:
18201
50DC
H
:
4719
H
3276.6
:
2786.6
32766
:
27866
7FFE
H
:
6CDA
H
Overrange
1820.0
:
0.0
18200
:
0
4718
H
:
0000
H
2786.5
:
32
27865
:
320
6CD9
H
:
0140
H
Nominal range
-0.1
:
-120.0
-1
:
-1200
FFFF
H
:
FB50
H
31.9
:
-184.0
319
:
-1840
013F
H
:
F8D0
H
Underrange
< -120.0
-32768
8000
H
< -184.0
-32768
8000
H
Underflow
Measuring range for thermocouple type E
Table 13-20 SIMATIC S7 format: Measuring range type E in °C and °F
Type E in °C
Units
Type E in °F
Units
Range
decimal hexadec‐
imal
decimal
hexa‐
decimal
> 1200.0
32767
7FFF
H
> 2192.0
32767
7FFF
H
Overflow
1200.0
:
1000.1
12000
:
10001
2EE0
H
:
2711
H
2192.0
:
1832.1
21920
:
18321
55A0
H
:
4791
H
Overrange
1000.0
:
-270.0
10000
:
-2700
2710
H
:
F574
H
1832.0
:
-454.0
18320
:
-4540
4790
H
:
EE44
H
Nominal range
< -270.0
- 32768
8000
H
< -454.0
- 32768
8000
H
Underflow
Analog electronic modules
13.8 Representation of analog values
ET 200iSP
Operating Instructions, 11/2017, A5E00247483-07
297