Properties
● Digital electronic module with two relay outputs
● Can only be inserted on terminal module TM-RM/RM, which means they can be used
starting from slot 5 in the standard ET 200iSP configuration and from slot 4 in a redundant
configuration. This configuration is checked by STEP 7.
● Output current 2 A per output
● Substitute value
● Suitable for solenoid valves, DC contactors, and indicator lights
● Isolated from the supply voltage
● NO contact
Note
If you connect an extra-low voltage system (SELV/PELF) to one channel of the relay
module, you can only use an extra-low voltage (SELV/PELF) on the other channel.
Pin assignment of actuators
Table 12-14 Pin assignment of actuators
Pin assignment and view
Remarks
&
&
6
6
&KDQQHO
&RQQHFWLRQ
H[DPSOH
Actuator terminals:
Channel 0: Terminals 1 and 2
Channel 1: Terminals 3 and 4
C
n
: Common 0, 1
NO
n
: NO contact 0, 1
Digital electronic modules
12.3 Digital electronic module 2 RO Relay UC60V/2A
ET 200iSP
Operating Instructions, 11/2017, A5E00247483-07
255