6. Swivel the Ex d isolating plug back into the horizontal position and push it back to the end
stop. Pay attention that the locking lever is flush with the plug and is engaged.
7. Label the electronic module using the labeling strips provided and reinsert the labeling strips
into the electronic module.
Note
If a gap (of an electronic module 2 DO Relay UC60V/2A) develops due to the ET 200iSP
configuration, the following rules apply:
● The gap is at the last slot of the ET 200iSP: insert the slot cover (or a reserve module
as of product version 3 or later) in this gap.
● The gap is at a different slot (for electronic module 2 DO Relay UC60/2A): insert a
reserve module (as of product version 3) in this gap.
Uninstalling electronic modules 2 DO Relay UC60V/2A
1. Follow steps 1 to 3, see "Digital electronic module 2 RO Relay UC60V/2A (Page 254)"
installing and labeling
2. Use the screwdriver to operate the catch on the underside of the electronic module.
3. Swivel this upward.
4. Remove the module from the storage space of the terminal module.
Wiring
5.5 Inserting and labeling the power supply, interface module, and electronic modules
ET 200iSP
130