Note the following:
● Save the service data directly after a ET 200sSP station has failed.
● Connect directly to IM 152 by means of PROFIBUS DP, RS 485-IS coupler and
PROFIBUS RS 485-IS
Note
Connect the programming device to the PROFIBUS DP and access the IM 152 via the RS
485-IS coupler (of the inherently safe PROFIBUS RS 485-IS).
In a redundant system, you need to establish the connection to only one of the two IM 152.
Procedure
1. From the SIMATIC Manager menu choose "Target system > Show available stations".
2. Select the affected station.
3. Select the "PLC > Save service data" command
In the next dialog box, select the file path and the file names for the service data.
4. Save the file.
5. Forward these files to Customer Support on request.
Maintenance
7.7 Reading service data
ET 200iSP
Operating Instructions, 11/2017, A5E00247483-07
193