● To work online with SIMATIC PDM, you require a PROFIBUS-DP interface, such as
CP5611 (6GK1561-1AA00). The CP must be set to the PROFIBUS-DP interface (in
SIMATIC Manager: menu command Options > Set PG/ PC Interface).
WARNING
If you are configuring with the GSD file and SIMATIC PDM, create your project in two
steps:
1. Step: Configuring by means of GSD file
2. Step: Setting Parameters with SIMATIC PDM
Note that configuration (step 1) is consistent with the parameter assignment with SIMATIC
PDM (step 2). The assignment of the slots from step 1 must match the parameters
generated with SIMATIC PDM (step 2).
Procedure for configuring
STEP 7 version 4.02 or higher
COM PROFIBUS version 5.0 or higher or another
project engineering software
1. Start SIMATIC Manager.
2. Integrate the GSD file into HW Config (see
requirements).
3. Configure the ET 200iSP with HW Config.
– Create a new project
– Drag modules from the hardware catalog
to the configuration table
4. Save the configuration, or download it to the
DP master.
1. Start COM PROFIBUS or the project
engineering software.
2. Integrate the GSD file into COM PROFIBUS or
into the engineering software (see
requirements).
3. Configure the ET 200iSP with COM
PROFIBUS / your project engineering
software.
4. Save the configuration and download the
configuration to the DP master.
Procedure for assigning parameters to electronic modules
1. Start SIMATIC Manager.
2. Select the process device network view as the standard view with the menu command
Options > Settings > View > Process Network View.
3. Create a new project with the menu command File > New. The "New" dialog opens in which
you enter the required project name and confirm with "OK".
4. Now select the Networks icon, right-click and select Insert New Object > PC and Insert New
Object > PROFIBUS DP Network.
5. In the left-hand pane of the window, select the PC icon. An icon labeled DP Interface now
appears in the right-hand pane of the window. Right-click on this icon and select "Object
Properties". In the next dialog, select "PROFIBUS-DP Networks" under networks and
confirm with "OK".
Commissioning and Diagnostics
6.3 Project Engineering with GSD File and SIMATIC PDM
ET 200iSP
138
Operating Instructions, 11/2017, A5E00247483-07