DANGER
The substitute values are stored in the flash memory of the IM 152. These are output at the
next startup of the ET 200iSP until it starts exchanging data with the DP master.
Remember this behavior if you change to a different project engineering environment with
the ET 200iSP.
Solution: Erase the flash memory of the IM 152 first.
12.5.3
Digital electronic module 2 DO Relay UC60V/2A
Parameters for 2 DO Relay UC60V/2A
Table 12-22 Parameters for 2 DO Relay UC60V/2A
Parameters
Range of values
Default
Applicability
Reaction to CPU/Master STOP
● Set substitute value
● Hold last value
Set substitute value
Channel
Substitute value
● 0
● 1
0
Channel
12.6
Description of the parameters of the digital electronic modules
12.6.1
Time stamping
Description
With this parameter, you can enable time stamping on a channel basis for each digital input
of the module. The time stamp will be passed from the ET 200iSP to the S7-400 or OS if you
also enable the "Time Stamp" parameter in the IM 152.
12.6.2
Pulse stretching
Description
Pulse extension is a function for changing a digital input signal. A pulse at a digital input is
extended to at least the configured length. If the input pulse is already longer than the
configured length, then the pulse will not be changed.
Digital electronic modules
12.6 Description of the parameters of the digital electronic modules
ET 200iSP
Operating Instructions, 11/2017, A5E00247483-07