x*5W = basic power loss of power supply (x = 1 for standard configuration, x = 2 for redundant
configuration)
1.2*∑
PV_Type_I/O
= typical power loss of input and output modules, including the resulting P
V
in
the power supply.
3.7
Maximum configuration of the ET 200iSP
Number of ET 200iSP Stations
You may operate up to 31 ET 200iSP stations on one segment of
PROFIBUS RS 485-IS (via RS 485-IS Coupler).
Power consumption of ET 200iSP with full configuration
Refer to technical specifications Power supply PS 24 VDC (Page 221) and technical
specifications Power supply PS 120/230 VAC (Page 224).
Width of ET 200iSP
The maximum configuration width ET 200iSP (power interface 32 electronic
m terminating module) is:
● 1.095 m (with one power supply and one IM 152)
● 1.185 m (with two power supplies and two IM 152)
Address space
The interface module supports maximum 244 input and 244 output bytes. There are DP
masters that do not control the entire address space.
Configuration options
3.7 Maximum configuration of the ET 200iSP
ET 200iSP
56
Operating Instructions, 11/2017, A5E00247483-07