Technical specifications
Interrupts
● Hardware interrupt
No
● Diagnostic interrupt
Yes, can be set
Diagnostic functions
● Group error display
Red "SF" LED
● Diagnostic information can be read
Yes
Monitoring for
● Short-circuit
R < 80 Ω (one output)
R < 40 Ω (outputs wired in parallel)
● Wirebreak
R
1
> 10 kΩ
I < 100 µA
Safety data
See EC-type-examination certificate
KEMA 04ATEX1249
Maximum values for intrinsically safe switching signal SO:
● U
i
28 V
● I
i
Not applicable
● P
i
1.2 W
● C
i
3 nF
● L
i
0 mH
Actuator selection data
No load voltage U
AO
● 4 DO DC23.1V/20mA SHUT DOWN "H"/ "L"
min. 23.1 V
● 4 DO DC17.4V/27mA SHUT DOWN "H"/ "L"
min. 17.4 V
● 4 DO DC17.4V/40mA SHUT DOWN "H"/ "L"
min. 17.4 V
Internal resistance R
i
● 4 DO DC23.1V/20mA SHUT DOWN "H"/ "L"
275 Ω
● 4 DO DC17.4V/27mA SHUT DOWN "H"/ "L"
150 Ω
● 4 DO DC17.4V/40mA SHUT DOWN "H"/ "L"
150 Ω
Curve vertices E for 4 DO DC23.1/20mA SHUT DOWN "H"/
"L"
● Voltage U
E
min. 17.1 V
● Current I
E
min 20 mA (one output)
Curve vertices E for 4 DO DC17.4/27mA SHUT DOWN "H"/
"L"
● Voltage U
E
min. 13.2 V
● Current I
E
min 27 mA (one output)
min. 54 mA (outputs switched in paral‐
lel)
Curve vertices E for 4 DO DC17.4/40mA SHUT DOWN "H"/
"L"
● Voltage U
E
min. 11.0 V
Digital electronic modules
12.2 Digital electronics module 4 DO
ET 200iSP
248