Parameter
Value
Slot reference junction 2
11
Input reference junction 2
RTD on channel 1
● Parameters relevant for 4 AI RTD and 4 AI TC:
Slot
Parameter
Value
8 (4 AI RTD)
Type/range of measurement I0
RTD-4 wire connection/ Pt 100
climatic range
11 (4 AI RTD)
Type/range of measurement I1
RTD-4 wire connection/ Pt 100
climatic range
15 (4 AI TC)
Reference junction I0
Yes
Reference junction I1/I2/I3
None
Reference junction number
2
Measuring range I0
Type...
Measuring range I1/I2/I3
(any)
22 (4 AI TC)
Reference junction I0/I1
Yes
Reference junction I2/I3
None
Reference junction number
1
Measuring range I0/I1
Type...
Measuring range I2/I3
(any)
32 (4 AI TC)
Reference junction I0
None
Reference junction I1
Yes
Reference junction I2/I3
None
Reference junction number
1
Measuring range I0
(any)
Measuring range I1
Type...
Measuring range I2/I3
(any)
Non-isolated thermocouples
When you use non-isolated thermocouples, you must comply with the permitted common-
mode voltage.
Analog electronic modules
13.9 Fundamentals of analog value processing
ET 200iSP
Operating Instructions, 11/2017, A5E00247483-07
305