Output ranges for current: 0 to 20 mA; 4 to 20 mA
Table 13-28 SIMATIC S7 format: Output ranges 0 to 20 mA; 4 to 20 mA
Output range
0 to 20 mA
Output range
4 to 20 mA
Units
Range
decimal
hexadecimal
0
0
> 32511
> 7EFF
H
Overflow
23,5178
22,8100
32511
7EFF
H
Overrange
:
:
:
:
20,0007
20,0005
27649
6C01
H
20,0000
20,0000
27648
6C00
H
:
:
:
:
Nominal range
0
4,0000
0
0
H
0
3,9995
-1
FFFF
H
Underrange
:
:
:
:
0
0
-6912
E500
H
0
0
< -6913
< E4FF
H
Underflow
13.9
Fundamentals of analog value processing
13.9.1
Wiring thermocouples
Introduction
This section contains additional information on connecting thermocouples.
Analog electronic modules
13.9 Fundamentals of analog value processing
ET 200iSP
Operating Instructions, 11/2017, A5E00247483-07
301