Status and error LEDs on the Watchdog module
Table 6-6
Status and error LEDs on the Watchdog module
LEDs
Meaning
Remedy
SF
Bit 0
on
Wrong module inserted or diagnostic message is present. Analyze the diagnostic data.
flashes The LED flashes at the assigned frequency (toggle: 0.1 Hz;
0.5 Hz; 1 Hz; 2 Hz)
---
on
Output signal (bit 0 active)
---
6.7
Commissioning and starting up the ET 200iSP
6.7.1
Safety Information
Safety Information
Note
During commissioning, keep to national regulations.
Always observe the guidelines according to EN 60 079-17 when performing operation checks.
This standard also contains the directives of international standard IEC 60 079-17.
Performing tests
Note
You must provide for the safety of your facility. Before a system undergoes final commissioning,
you should perform a complete function test and the necessary safety tests.
Incorporate foreseeable errors when planning the tests. This will enable you to avoid
endangering persons or property during operation.
Commissioning and Diagnostics
6.7 Commissioning and starting up the ET 200iSP
ET 200iSP
Operating Instructions, 11/2017, A5E00247483-07
147