Restarting following an update
In the STEP 7 user interface you can decide whether
● the IM 152 is reset automatically following a successful update so that it can start up with
the newly loaded firmware.
CAUTION
If there is a check mark in the "Activate firmware after download" box, there is a brief ET
200iSP station failure. If you have not made any provisions for this situation, the update
will cause to CPU to go to STOP mode due to a rack failure.
● the IM 152 will be reset by turning of the power supply before the IM 152 starts up with the
new firmware after turning on the power supply again.
Update
If the update fails, the IM 152 always restarts with its current ("old") FW version after the supply
voltage is switched off and then on again. See table
Status and Error LEDs on the IM 152.
See also
Status and error LEDs on the ET 200iSP (Page 142)
7.7
Reading service data
Properties
If you need to contact our Customer Support due to a service event, the department may
require specific information on the status of an ET 200iSP station in your system for diagnostic
purposes. This information is available as of FW version V2.0.5 of the IM 152 in the service
data.
Select the “Target system -> Save service data” command to read this information and save
the data to a file to forward to Customer Support.
Requirements
Installation of STEP 7 version 5.3 or higher.
Maintenance
7.7 Reading service data
ET 200iSP
192
Operating Instructions, 11/2017, A5E00247483-07