Pt 100 cli‐
mate in °C
(1 digit =
0.01°C)
Units
Pt 100 cli‐
mate in °F
(1 digit =
0.01 °F)
Units
Range
decimal
hexa‐
decimal
decimal
hexa‐
decimal
-120.01
:
-145.00
-12001
:
-14500
D11F
H
:
C75C
H
-184.01
:
-229.00
-18401
:
-22900
B81F
H
:
A68C
H
Underrange
< - 145.00
-32768
8000
H
< - 229.00
-32768
8000
H
Underflow
Measuring ranges for resistance thermometer Ni 100 standard
Table 13-17 SIMATIC S7 format: Measuring ranges Ni 100 standard in °C and °F
Ni 100
standard in
°C (1 digit =
0.1°C)
Units
Ni 100
standard in
°F (1 digit =
0.1 °F)
Units
Range
decimal
hexa‐
decimal
decimal
hexa‐
decimal
> 295.0
32767
7FFF
H
> 563.0
32767
7FFF
H
Overflow
295.0
2950
B86
H
563.0
5630
15FE
H
Overrange
:
:
:
:
:
:
250.1
2501
9C5
H
482.1
4821
12D5
H
250.0
2500
9C4
H
482.0
4820
12D4
H
:
:
:
:
:
:
Nominal range
-60.0
-600
FDA8
H
-76.0
-760
FD08
H
-60.1
-601
FDA7
H
-76.1
-761
FD07
H
Underrange
:
:
:
:
:
:
-105.0
-1050
FBE6
H
-157.0
-1570
F9DE
H
< -105.0
-32768
8000
H
< -157.0
-32768
8000
H
Underflow
Measuring ranges for resistance thermometer Ni 100 climate
Table 13-18 SIMATIC S7 format: Measuring ranges Ni 100 climate in °C and °F
Ni 100 cli‐
mate in °C
(1 digit =
0.01°C)
Units
Ni 100 cli‐
mate in °F
(1 digit =
0.01 °F)
Units
Range
decimal
hexa‐
decimal
decimal
hexa‐
decimal
> 295.00
32767
7FFF
H
> 325.11
32767
7FFF
H
Overflow
295.00
:
250.01
29500
:
25001
733C
H
:
61A9
H
327.66
:
280.01
32766
:
28001
7FFE
H
:
6D61
H
Overrange
250.00
:
-60.00
25000
:
-6000
61A8
H
:
E890
H
280.00
:
-76.00
28000
:
-7600
6D60
H
:
E250
H
Nominal range
Analog electronic modules
13.8 Representation of analog values
ET 200iSP
296