Technical specifications
Output current for 120 VAC (85 VAC to 132 VAC) and
ambient temperature
● From -20°C to +70°C with horizontal installation and
-20°C to +50°C for all other installation positions
max. 3A
● from -20°C to +60°C with horizontal installation
max. 4A
● -20°C to +50°C with horizontal installation
max. 5A
Status, interrupts, diagnostics
Status display
yes (on IM 152)
Interrupts
No
Diagnostic functions
● Group error display
No
● Diagnostic information can be read
yes (over IM 152)
Safety data
See EC-type-examination certificate
KEMA 09ATEX0156
U
M
264V DC, 264V AC
1
Available soon
2
Tolerance range 85 VAC to 264 VAC.
Fusing with 6 A automatic circuit breaker and tripping characteristic C (for each ET 200iSP station)
3
Rated current: 0.75A (for 120 VAC)/ 0.45A (for 230 VAC)
4
You can find additional information about in the section "Restricted Number of Connectable Electronics
Note
Take appropriate measures to ensure that U
m
= 264 VDC, 264 VAC is not exceeded.
Power Supply
10.2 Power supply PS 120/230 VAC
ET 200iSP
226
Operating Instructions, 11/2017, A5E00247483-07