3. Secure the individual wires in the screw-type terminal Ex e.
4. Close the terminal cover.
3
①
Terminal module TM-RM/RM
②
Connection for electronic module 2 DO Relay UC60V/2A
channels 0 and 1
③
Terminal cover
Figure 5-9
Wiring terminal module TM-RM/RM
For pin configuration, refer to Chapter "Terminal module TM-RM/RM 60S".
5.4.9
Connecting cable shields
Properties
The cable shields of the analog electronic modules must be connected to the ground bus
(equipotential bonding) of the enclosure.
Prerequisites
● Tim-plated or galvanized standard mounting rail complying with EN 50022 (35 x 15/ 35 x
7.5) and fittings
● Shield terminals (6ES5728-8MA11)
● Securing the ground cable to the standard mounting rail:
– Zone 1 or zone 21: Ex e terminal. Use the terminal WP 16/E, from Weidmüller (see
appendix "AUTOHOTSPOT").
– Zone 2, zone 22 or safe area: Normal terminal
Wiring
5.4 Wiring the ET 200iSP
ET 200iSP
120
Operating Instructions, 11/2017, A5E00247483-07