Parameters for configuration "4 AI I 2W+x, "4 AI I 4W+x"
In addition to configuration "4 AI I 2WIRE HART" and "4 AI I 4WIRE HART": the following
parameters can be set with the configurations "...W+x":
Table 13-35 Parameters for configuration "...W+x"
Parameter
Range of values
Default
Applicability
2 AI I 2WIRE HART
2 AI I 4WIRE HART
HART retries (number of retries)
0 to 10
2
Module
HART Fast Mode
● enabled
● disabled
disabled
Module
Channel
● 0
● 1
● 2
● 3
0
Channel
IEEE tag
● None
● Primary variable
● 1. Auxiliary variable
● 2. Auxiliary variable
● 3. Auxiliary variable
None
Channel
HART warning
● enabled
● disabled
disabled
Module
HART diagnostics
● enabled
● disabled
disabled
Module
Analog electronic modules
13.11 Parameters of the analog electronic modules
ET 200iSP
Operating Instructions, 11/2017, A5E00247483-07
319