Parameters for configuration "4AO I HART"
Table 13-37 Parameters for configuration "4AO I HART"
Parameter
Range of values
Default
Applicability
Group diagnostics
● enabled
● disabled
enabled
Module
Diagnostics: wire break
● enabled
● disabled
enabled
Channel
Diagnostics: wire break
● enabled
● disabled
enabled
Channel
Output range
● Disabled
● 0 mA to 20 mA
● 4 mA to 20 mA
● HART
HART
Channel
Response to CPU/ master STOP
● Zero output
current/voltage
● Set substitution
value
● Hold last value
Set substitution
value
Channel
Substitution value
Every value of the
nominal range
0 to 20 mA: 0 mA
4 to 20 mA and
HART: 4 mA
Channel
WARNING
The substitute values are stored in the flash memory of the IM 152. These are output at the
next startup of the ET 200iSP until it starts exchanging data with the DP master.
Remember this behavior if you change to a different project engineering environment with
the ET 200iSP.
Solution: Erase the flash memory of the IM 152 first.
Parameters for configuration "...I +x"
In addition to the "4AO I HART" configuration, the following parameters can be set for the
"...I +x" configurations:
Table 13-38 Parameters for configuration "I +x"
Parameter
Range of values
Default
Applicability
HART retries (number of retries)
0 to 10
2
Module
HART Fast Mode
● enabled
● disabled
disabled
Module