3.17.3
Configuring frequency meters
Procedure in HW Config
Drag the configuration "2 Trace/ 6 DI NAMUR" from the hardware catalog to the configuration
table with the mouse or set the configuration with the parameters.
"2 Trace/ 6 DI NAMUR" configuration:
● Assignment of the digital inputs on the 8 DI NAMUR electronic module
For further information on input assignments, refer to the technical data for the 8 DI NAMUR
electronic module.
Table 3-13
Assignment of the digital inputs for 2 Trace/ 6 DI NAMUR
Digital input
Terminal
Assignment
Channel 0
1, 2
Frequency counter 1
Channel 1
5, 6
Frequency counter 2
Channel 2
9, 10
Digital input 2
Channel 3
13, 14
Digital input 3
Channel 4
3, 4
Digital input 4
Channel 5
7, 8
Digital input 5
Channel 6
11, 12
Digital input 6
Channel 7
15, 16
Digital input 7
Configuration options
3.17 Metering frequencies
ET 200iSP
Operating Instructions, 11/2017, A5E00247483-07
77