Sprinkler Identification Number
SIN C5337

Approvals
UL and C-UL Listed. NYC Approved.
(Refer to Table 1. The approvals apply
only to the service conditions indicated
in the Design Criteria Section)

Maximum Working Pressure
175 psi (12,1 bar)

Pipe Thread Connection
3/4 inch NPT

Discharge Coefficient
K = 11.2 GPM/psi

1/2

 (161,3 LPM/bar

1/2

)

Temperature Ratings
200

°

F/93

°

C

Finishes
Sprinkler: White Polyester, Chrome
Plated, or Natural Brass

Physical Characteristics
The Model ELO SW-24 ECOH
Horizontal Sidewall Sprinklers utilize a
dezincification resistant (DZR) bronze
frame and a 3 mm bulb. The two-
piece button assembly is brass and
copper. The sprinkler frame orifice is
sealed with a  gasketed spring plate
(Belleville Seal) consisting of a
beryllium nickel disc spring that is
sealed on both its inside and outside
edges with a Teflon

TM

 gasket. The

compression screw is bronze, & the
deflector is brass.

Tyco Fire Products --- www.centralsprinkler.com
451 North Cannon Avenue, Lansdale, Pennsylvania 19446 --- USA
Customer Service/Sales: Tel: (215) 362-0700 / Fax: (215) 362-5385
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500

Model ELO SW-24

11.2 K-factor
Standard Response
Extended Coverage Ordinary Hazard

Horizontal Sidewall Glass Bulb Automatic Sprinklers

No. 2-11.5

General
Description

The Central Model ELO SW-24,
11.2 K-factor, Standard Response,
Extended Coverage Ordinary Hazard
(ECOH) Horizontal Sidewall Sprin-
klers are decorative glass bulb
sprinklers designed for use in ordinary
hazard occupancies per NFPA 13.

They are designed for installation
along a wall beneath smooth & level
ceilings as defined in the applicable
installation standard. Horizontal
sidewall sprinklers are generally used
in lieu of pendent sprinklers because
of aesthetic, building construction, or
installation economy considerations.

Operation: The glass bulb contains a
fluid which expands when exposed to
heat. When the rated temperature is
reached, the fluid expands sufficiently
to shatter the glass bulb, which then
allows the sprinkler to activate & flow
water.

WARNING

The Model ELO SW-24 ECOH
Horizontal Sidewall Sprinklers
described herein must be installed &
maintained in compliance with this
document, as well as with the
applicable standards of the National
Fire Protection Association, in
addition to the standards of any other
authorities having jurisdiction. Failure
to do so may impair the integrity of
these devices.

The owner is responsible for
maintaining their fire protection
system and devices in proper
operating condition. The installing
contractor or sprinkler manufacturer
should be contacted relative to any
questions.

Technical
Data

CENTRAL

ELO SW-24

2-01

Extended
Coverage
Ordinary Hazard
Horizontal
Sidewall
Sprinklers

I M

A

O

P

T

OBSOLETE

Summary of Contents for CENTRAL ELO SW-24

Page 1: ...ption The Central Model ELO SW 24 11 2 K factor Standard Response Extended Coverage Ordinary Hazard ECOH Horizontal Sidewall Sprin klers are decorative glass bulb sprinklers designed for use in ordinary hazard occupancies per NFPA 13 They are designed for installation along a wall beneath smooth level ceilings as defined in the applicable installation standard Horizontal sidewall sprinklers are ge...

Page 2: ...ated within the maximum protection area of any other sprinkler These sprinklers may be installed on sloped ceilings in loading docks with a maximum roof slope of 4 inches per foot as indicated in Figure 3 of this data sheet The Model ELO SW 24 ECOH Horizontal Sidewall Sprinklers may be used with any metalic flush or extended escutcheon provided the maximum ceiling and or wall to top of sprinkler d...

Page 3: ...e high point of the slope with its deflector parallel to the slope Ref Figure 3 The Model ELO SW 24 ECOH Horizontal Sidewall Sprinklers must be maintained and serviced in accordance with the following instruc tions NOTES Absence of an escutcheon which is used to cover a clearance hole may delay the time to operation in a fire situation Before closing a fire protection system main control valve for...

Page 4: ...ion or which have not been installed maintained modified or repaired in accordance with applicable Standards of the National Fire Protection Association and or the standards of any other Authorities Having Jurisdic tion Materials found by Tyco Fire Products to be defective shall be either repaired or replaced at Tyco Fire Products sole option Tyco Fire Products neither assumes nor authorizes any p...

Reviews: