Table 12-16 Permitted switching frequency for max. 1000 switching operations
Resistive load
Voltage
Current (max.)
Switching frequency
(max.)
For ohmic load, inductive load to
L/R = 10 ms
24 VDC
2.0 A
1 Hz
1.0 A
1 Hz
60 VDC
0.5 A
1 Hz
60 VAC
2.0 A
0.5 Hz
1.0 A
1 Hz
For inductive load in accordance
with IEC 947-5-1 DC 13/ AC15
24 VDC
2.0 A
0.2 Hz
1.0 A
0.5 Hz
60 VDC
0.5 A
0.5 Hz
60 VAC
2.0 A
0.2 Hz
1.0 A
0.5 Hz
Note
The voltage feed to the relay outputs is fuse-protected with a 6 A automatic circuit breaker with
tripping characteristic C.
12.4
Identification and Message Functions (I&M)
Description
Refer to the Chapter "Identification Data I&M (Page 58)".
12.5
Parameters of the digital electronic modules
12.5.1
Digital electronic module 8 DI NAMUR
Configuration with STEP 7 as of version 5.3 Service Pack 1 and current HW update
For a description, refer to the online help for STEP 7.
Configuration with GSD file
For digital electronic module 8 DI NAMUR, there are various configurations that you can select
using the following entries in the hardware catalog of the configuration software:
● "8 DI NAMUR" configuration: 8 digital inputs
● "2 Count/ 6 DI NAMUR" configuration: 2 counters and 6 digital inputs
Digital electronic modules
12.5 Parameters of the digital electronic modules
ET 200iSP
Operating Instructions, 11/2017, A5E00247483-07
259