Wiring rules for ...
TM-PS-A/ TM‑PS-A UC,
TM-PS-B/ TM-PS-B UC
TM-IM/EM, TM-EM/EM
(spring and screw termi‐
nals)
With insulation collar 0.25
to 1.5 mm
Form E, up to 12 mm long Form E, up to 12 mm long
Tightening torque
0.5 - 0.7 Nm
5.4.2
Wiring Terminal Modules with Screw Terminals
Properties
● In terminal modules with screw terminals, the individual wires are screwed into the terminal.
● Wire-end ferrules are not necessary.
Prerequisites
Observe the wiring rules.
Required tool
3.5 mm screwdriver
Procedure
1. Strip insulation from the wires.
2. Insert the individual wires into the terminal.
3. Tighten the screw. Result: The wire is clamped into the terminal module.
5.4.3
Wiring terminal modules with spring terminals
Properties
In terminal modules with spring terminals, the individual wires are affixed by inserting them
into the terminal.
Requirements
Observe the wiring rules.
Required tools
3.5 mm screwdriver
Wiring
5.4 Wiring the ET 200iSP
ET 200iSP