Shipping and storage conditions
The distributed I/O station ET 200iSP exceeds the requirements of IEC 61131-2 for transport
and storage conditions. The following data applies to modules which are transported or stored
in the original packaging.
Type of condition
permissible range
at user's discretion
≤ 1 m
Temperature
from - 40 °to + 70 °C
Temperature change
20 K/h
Barometric pressure
from 1080 to 660 hPa (corresponds to a height of
-1000 to 3500 m)
Relative humidity
from 5 to 95%, without condensation
See also
General Rules and Regulations for Wiring (Page 103)
8.4
Mechanical and climatic environmental conditions
Operating conditions
The ET 200iSP is designed for stationary use in weather-proof locations. The operating
conditions surpass requirements to DIN IEC 60721-3-3.
● Class 3M3 (mechanical requirements)
● Class 3K3 (climatic requirements)
Climatic environmental conditions
The following climatic environmental conditions apply:
Environmental conditions
Areas of application
Remarks
Temperature
from -20 to 70°C
1 2
For horizontal installation
from -20 to 50°C
1 2
For all other mounting positions
Temperature change
10 K/h
-
Relative humidity
5 to max. 95 %
Without condensation
Barometric pressure
From 1,080 hPa to 795 hPa
Corresponds with an altitude of -1000
m to 2000 m
Concentration of pollutants
SO
2
: < 0.5 ppm;
rel. humidity < 60 %, no condensation
H
2
S: < 0.1 ppm;
rel. humidity < 60 %, no condensation
Test:
10 ppm; 4 days
1 ppm; 4 days
ISA-S71.04 severity level G1; G2; G3
-
1
Output current of power supply PS 24 VDC (6ES7 138-7EA01-0AA0): Power supply PS 24 VDC (Page 221)
2
General technical specifications
8.4 Mechanical and climatic environmental conditions
ET 200iSP
200