Parameters for 8 DI NAMUR, "2 Trace/ 6 DI NAMUR" configuration
The following parameters can be set for the frequency meter in addition to the "8 DI NAMUR"
configuration:
Table 12-20 Parameters for "2 Trace/ 6 DI NAMUR"
Parameters
Range of values
Default
Applicability
Sensor type frequency in‐
puts
● Channel disabled
● NAMUR sensor
● Single contact, no load
resistance
NAMUR sensor
Channel
Metering window (GATE)
● 50 ms
● 200 ms
● 1 s
1 s
Channel
12.5.2
Digital electronic module 4 DO
Parameters for 4 DO
Table 12-21 Parameters for 4 DO
Parameters for
SHUT DOWN "H"
modules
Parameters for
SHUT DOWN "L"
modules
Range of values
Default
Applicability
Switch channels in parallel
1
● Yes
● No
No
Channel 0
Channel 2
Reaction to CPU/Master STOP
● Set substitute value
● Hold last value
Set substitute value
Channel
Substitute value
● 0
● 1
0
Channel
Group diagnostics
● enabled
● disabled
enabled
Channel
Diagnostics of wire-break
2
● enabled
● disabled
enabled
Channel
Diagnostics: wire break
● enabled
● disabled
enabled
Channel
---
Deactivate shutdown
signal
3
● enabled
● disabled
disabled
Module
1
Not supported for 4DO DC23.1V/20mA.
2
Wire break is detected only with a "1" signal for the digital output module.
3
Only possible with SIMATIC PDM and in HW Config with order numbers followed by "*".
Digital electronic modules
12.5 Parameters of the digital electronic modules
ET 200iSP
262
Operating Instructions, 11/2017, A5E00247483-07