At channels 0 and 1 change the sensor type to "NAMUR sensor." Select "disabled" for all other
channels.
Figure 2-8
Disabling ET 200iSP Channels
Step 4
Follow the same procedure as described in item 3 for each of the ET 200iSP modules, and
make the changes as outlined in the table below.
Table 2-2
Changes
Module
Slot
Type
Channel 0
Channel 1
Channel 2- 7
1
4
8 x DI NAMUR
NAMUR sensor
NAMUR sensor
Sensor type: disabled
2
5
8 x DI NAMUR
NAMUR sensor
Sensor type: Channel dis‐
abled
Sensor type: disabled
3
6
4 x DO
No change
No change
---
4
7
4 x DO
No change
No change
---
5
8
4 x DO
No change
No change
---
Step 5
Save the configuration with File > Save and download it to the CPU withPLC > Download.
Commissioning guideline
2.9 Configuring the Example
ET 200iSP
40