Measuring range for thermocouple type T
Table 13-26 SIMATIC S7 format: Measuring range type T in °C and °F
Type T in °C
Units
Type T in °F
Units
Range
decimal
hexa‐
decimal
decimal
hexa‐
decimal
> 540.0
32767
7FFF
H
> 1004.0
32767
7FFF
H
Overflow
540.0
:
400.1
5400
:
4001
1518
H
:
0FA1
H
1004.0
752.1
10040
7521
2738
H
1DC1
H
Overrange
400.0
:
-270.0
4000
:
-2700
0FA0
H
:
F574
H
752.0
:
-454.0
7520
:
-4540
1D60
H
:
EE44
H
Nominal range
< -270.0
-32768
8000
H
< -454.0
-32768
8000
H
Underflow
Measuring range for thermocouple type U
Table 13-27 SIMATIC S7 format: Measuring range type U in °C and °F
Type U in °C
Units
Type U in °F
Units
Range
decimal
hexa‐
decimal
decimal
hexa‐
decimal
> 850.0
32767
7FFF
H
> 1562.0
32767
7FFF
H
Overflow
850.0
:
600.1
8500
:
6001
2134
H
:
17771
H
1562.0
1112.1
15620
11121
3D04
H
2B71
H
Overrange
600.0
:
-200.0
2000
:
-2000
1770
H
:
F830
H
1112.0
:
-328.0
11120
:
-3280
2B70
H
:
F330
H
Nominal range
< -200.0
-32768
8000
H
< -328.0
-32768
8000
H
Underflow
13.8.4
Output ranges of the analog output modules in S7 format
Introduction
The tables in this section contain the digitized analog values for the measuring ranges of the
analog output modules.
The binary representation of the analog values is always the same, so these tables only
compare the output ranges and the units.
Analog electronic modules
13.8 Representation of analog values