Safety data
See EC-type-examination certificate
KEMA 04ATEX2242
9.5
Terminal modules TM-EM/EM 60S and TM-EM/EM 60C
Order number
6ES7193-7CA00-0AA0 (screw terminal)
6ES7193-7CA10-0AA0 (spring terminal)
6ES7193-7AA20-0AA0 (black terminal)
6ES7193-7CA20-0AA0 (black terminal)
For use in safe areas and identification of non-intrinsically safe signals, the terminal modules
are also available in a version with black terminals.
Note that the following rules for their use still apply:
1. Within an ET 200iSP station, terminal modules with blue terminals and terminal modules
with black terminals may not to be combined.
Combining the terminals will not meet the requirements regarding explosion protection.
2. An ET 200iSP station which is constructed only with black terminals and an ET 200iSP
station which is constructed only with blue terminals may not be connected to the same RS
485-iS coupler.
Combining the terminals will not meet the requirements regarding explosion protection.
Terminal modules
9.5 Terminal modules TM-EM/EM 60S and TM-EM/EM 60C
ET 200iSP
Operating Instructions, 11/2017, A5E00247483-07