Technical specifications
Basic error limit (operational limit at 25°C, relative to the
input range)
±0.1%
Temperature error (relative to the input range)
± 0.005%/K
Linearity error (relative to the input range)
±0.015%
Repeatability
(in steady state at 25 °C, relative to the input range)
±0.01%
Status, interrupts, diagnostics
Interrupts
● Diagnostic interrupt
Yes, can be set
Diagnostic functions
● Group error display
Red "SF" LED
● Diagnostic information can be read
Yes
Monitoring for
● Short-circuit
I
load
> 1 mA
R
load
< 30...60 Ω
● Wirebreak
I
load
> 1 mA
R
load
< 0.68...24 kΩ
1
Injection of substitute values
Yes, can be set
Safety information
See EC Prototype Certificate
KEMA 04ATEX1250
Actuator selection data
Output ranges (rated values)
● Current
0 to 20 mA
4 to 20 mA
Load impedance (in the rated output range)
Max. 750 Ω
Connection of actuators
● for current measurement
2-wire connection
supported
1
Wire break depends on current of the load
13.7
Identification and Message Functions (I&M)
Description
Refer to the Chapter "Identification Data I&M (Page 58)".
Analog electronic modules
13.7 Identification and Message Functions (I&M)
ET 200iSP
290
Operating Instructions, 11/2017, A5E00247483-07