Replacing a defective electronic module
You have already uninstalled the electronic module:
1. remove the removable part of the coding element from the new electronic module. The
coding element is located on the underside of the electronic module.
2. Install the new electronic module (same type) on the terminal module, checking for an
audible latching sound.
3. Follow steps 4 to 7, see "Digital electronic module 2 RO Relay UC60V/2A (Page 254)"
installing and labeling
Note
Check the coding element before you install the new interface or electronic module.
5.6
Setting the PROFIBUS address
Properties
With the PROFIBUS DP address, you define under which address the distributed I/O station
ET 200iSP is addressed on the PROFIBUS RS 485-IS.
Requirements
● The PROFIBUS DP address for the ET 200iSP is set on the interface module by means of
DIP switch. The DIP switch is located on the front of the interface module, protected by a
swivel cover.
● Permitted PROFIBUS DP addresses are 1 to 125
● Each address can be assigned only once on the PROFIBUS.
Required tool
3.5 mm screwdriver
Setting PROFIBUS DP Addresses
1. To open, swivel the cover to the right.
2. Use the screwdriver to set the desired PROFIBUS DP address by means of the DIP switch.
3. Close the cover.
Wiring
5.6 Setting the PROFIBUS address
ET 200iSP
Operating Instructions, 11/2017, A5E00247483-07