21-31
Setting the Input/Output Conditions
21
When "MANUAL" is selected on the "CALIBRATION" line
1. Move the cursor to "
CURSOR1-COORD" and press the SET key.
2. While the cursor is on the "
CROSS
CURSOR" line on the CROSS CURSOR
screen, press the SET key. Move the
crosshair cursor to the tick marks on the ruler
using the up/down/left/right arrow keys and set
coordinate 1.
3. Then move the cursor on the CROSS
CURSOR screen to the "
CUSOR2-
COORD" line and set coordinate 2 using the
same procedure.
4. Select the "
SCALE" line and enter the actual value of the distance between coordinates 1 and
2. In this example, the distance is 10 mm. Therefore, enter "10."
5. Select the "
SCALE(UNIT)" line and select the unit of distance between coordinates 1 and 2. In
this example, select "mm."
6. Select the "
REG" (register) line and while the cursor is on "EXEC" (execute) press the SET
key again. The controller will be calibrated to read "1 pixel = 1 mm."
CLOSS CURSOR RESET RETURN