Appendix G: Old PX3 Character LCD Display
737
Below illustrates the residual current information shown on the LCD
display.
Section
Example information
The inlet containing RCM sensor is INLET 1.
This residual current is 0 mA.
ALARM always displays for residual current sensor.
LEAK always displays for residual current sensor.
Measurement units are mA.
To run RCM self-test:
1.
Press the MODE button until the LCD alternates between "SLF" and
"tSt," which means SELF TEST.
2.
Press the FUNC button to start RCM self-test.
3.
The LCD shows dash symbols during RCM self-test.
4.
Upon completion, RCM self-test results are displayed for 30 seconds,
or until you press any button.
PAS: Self-test passed.
FAL: Self-test failed (the PX3 also beeps).
Below illustrates the RCM self-test mode.
Section
Example information
The inlet containing RCM sensor is INLET 1.