Appendix F: PX3 Models with Residual Current Monitoring
710
Setting RCM Current Thresholds
The RCM current thresholds define the critical, warning and normal
range of residual current.
To configure the RCM current thresholds and run self-test:
1.
Click Inlet to open the Inlet page.
2.
In the Residual Current Monitor section, click Setup.
3.
Set up RCM thresholds.
a.
Enable or disable the RCM critical threshold. Residual current
greater than this value triggers Critical RCM state.
b.
Enable or disable the RCM warning threshold. Residual current
greater than this value triggers Warning RCM state.
c.
Determine the residual current decrease to end Warning or
Critical RCM state.
d.
Click Save.
4.
Click 'Start Self Test' to run RCM self-test.
Scheduling RCM Self-Test
You can have the PX3 run RCM self-test automatically at a regular time
interval or on a specific date and time. See
Scheduling an Action
(on
page 351) for the procedure and select "Start residual current monitor
self test" to create the scheduled RCM self-test action.