Chapter 8: Using the Command Line Interface
586
Changing the Sensor Description
This command provides a description for a specific environmental
sensor.
config:#
externalsensor <n> description "<description>"
Variables:
<n> is the ID number of the environmental sensor that you want to
configure. The ID number is available in the PX3 web interface or
using the command "
show externalsensors <n>
" in the CLI. It is
an integer between 1 and 32.
<description> is a string comprising up to 64 ASCII printable
characters, and it must be enclosed in quotes.
Using Default Thresholds
This command determines whether default thresholds, including the
deassertion hysteresis and assertion timeout, are applied to a specific
environmental sensor.
config:#
externalsensor <n> useDefaultThresholds <option>
Variables:
<n> is the ID number of the environmental sensor that you want to
configure. The ID number is available in the PX3 web interface or
using the command "
show externalsensors <n>
" in the CLI. It is
an integer between 1 and 32.
<option> is one of the options:
true or false.
Option
Description
true
Default thresholds are selected as the threshold
option for the specified sensor.
false
Sensor-specific thresholds are selected as the
threshold option for the specified sensor.
Summary of Contents for PX3-3000 series
Page 5: ......
Page 18: ...Contents xviii Index 841...
Page 93: ...Chapter 4 Connecting External Equipment Optional 69...
Page 787: ...Appendix J RADIUS Configuration Illustration 763 Note If your PX3 uses PAP then select PAP...
Page 792: ...Appendix J RADIUS Configuration Illustration 768 14 The new attribute is added Click OK...
Page 793: ...Appendix J RADIUS Configuration Illustration 769 15 Click Next to continue...
Page 823: ...Appendix K Additional PX3 Information 799...