Chapter 8: Using the Command Line Interface
596
<hy_value> is a numeric value that is assigned to the hysteresis for
the specified inlet pole sensor. See
"To De-assert" and
Deassertion Hysteresis
(on page 798).
<as_value> is a number in samples that is assigned to the assertion
timeout for the specified inlet pole sensor. See
"To Assert" and
Assertion Timeout
(on page 796).
Commands for Overcurrent Protector Sensors
A sensor configuration command for overcurrent protectors begins with
sensor ocp.
You can configure various overcurrent protector threshold settings at a
time by combining multiple commands. See
Multi-Command Syntax
(on
page 617).
Set the Upper Critical threshold for an overcurrent protector:
config:#
sensor ocp <n> <sensor type> upperCritical <option>
Set the Upper Warning threshold for an overcurrent protector:
config:#
sensor ocp <n> <sensor type> upperWarning <option>
Set the Lower Critical threshold for an overcurrent protector:
config:#
sensor ocp <n> <sensor type> lowerCritical <option>
Set the Lower Warning threshold for an overcurrent protector:
config:#
sensor ocp <n> <sensor type> lowerWarning <option>
Set the deassertion hysteresis for an overcurrent protector:
config:#
sensor ocp <n> <sensor type> hysteresis <hy_value>
Set the assertion timeout for an overcurrent protector:
Summary of Contents for PX3-3000 series
Page 5: ......
Page 18: ...Contents xviii Index 841...
Page 93: ...Chapter 4 Connecting External Equipment Optional 69...
Page 787: ...Appendix J RADIUS Configuration Illustration 763 Note If your PX3 uses PAP then select PAP...
Page 792: ...Appendix J RADIUS Configuration Illustration 768 14 The new attribute is added Click OK...
Page 793: ...Appendix J RADIUS Configuration Illustration 769 15 Click Next to continue...
Page 823: ...Appendix K Additional PX3 Information 799...