Chapter 6: Using the Web Interface
362
3.
To make the PX3 record the firmware update failure event in the
internal log, select "System Event Log Action" in the Available
Actions field.
Sample Outlet-Level Event Rule
In this example, we want the PX3 to send SNMP notifications to the
SNMP manager for any sensor change event of outlet 3.
The event rule involves:
Event: Outlet > Outlet 3 > Sensor > Any sub-event
Action: System SNMP Notification Action
To create this outlet-level event rule:
1.
For an event at the outlet level, select "Outlet" in the Event field.
2.
Select "Outlet 3" because that is the desired outlet.
3.
Select "Sensor" to refer to sensor-related events.
4.
Select "Any sub-event" to include all events related to all sensors of
this outlet and all thresholds, such as current, voltage, upper critical
threshold, upper warning threshold, lower critical threshold, lower
warning threshold, and so on.
5.
To make the PX3 send SNMP notifications, select "System SNMP
Notification Action" in the Available Actions field.