Chapter 6: Using the Web Interface
364
3.
Select "Any sub-event" to include all events related to all sensors of
this inlet and all thresholds, such as current, voltage, upper critical
threshold, upper warning threshold, lower critical threshold, lower
warning threshold, and so on.
4.
To make the PX3 send SNMP notifications, select "System SNMP
Notification Action" in the Available Actions box.
Note: The SNMP notifications may be SNMP v2c or SNMP v3
traps/informs, depending on the settings for the System SNMP
Notification Action. See
Enabling and Configuring SNMP
(on page
Then the SNMP notifications are sent when:
Any numeric sensor's reading enters the warning or critical
range.
Any sensor reading or state returns to normal.
Any sensor becomes unavailable.
The active energy sensor is reset.
For example, when the Inlet I1's voltage exceeds the upper warning
threshold, the SNMP notifications are sent, and when the voltage
drops below the upper warning threshold, the SNMP notifications are
sent again.