Chapter 6: Using the Web Interface
385
Field
Description
Polling interval
Type a polling interval to determine how often the PX3 is
queried in the Cisco EnergyWise domain.
Range from 30 to 600 ms.
Default is 180 ms.
3.
Click Save in the
EnergyWise section.
For PX3-3000, PX3-4000, and PX3-5000 series, the parent/child
relationship is formed after the Cisco EnergyWise feature is enabled.
The PDU becomes a parent domain member.
All outlets become children of the PDU.